The Flexim FLUXUS G532 ST-LT, is a tailor-made solution for all typical applications for saturated steam up to a temperature of 356°F. Measuring the volume of steam from outside the pipe in a non-intrusive manner. For users, this means important advantages when considering the total cost of operating a measuring point: Simple installation without cutting or welding work on the pipeline. No downtime necessary - the system remains fully available for current production, without any production losses. The transit time difference principle already works at 0.03 ft/s and does not need any reduction to the diameter of the pipe to artificially increase the flow velocity. This means there is no loss of pressure, and accordingly no loss of energy.
Fluid Type: Saturated and superheated steam
Accuracy: Measurement uncertainty of the measuring system (volumetric flow rate): ±0.3 of reading ±0.005 m/s ( ±0.02 ft/s)Measurement uncertainty at the measuring point (volumetric flow rate):: ±1 to 3 % of reading ±0.005 m/s (±0.02 ft/s)
Repeatability: 0.15 % of reading ±0,005 m/s (±0.02 ft/s)
Flow channels: 1
Range: Flow Velocity Range: 0.01…60 m/s (0.03 to 197 ft/s) depending on the pipe diameter and sensor
Certifications/approvals: Ordloc (FM)
Power supply: 90 to 250 VAC / 50 to 60 Hz11 to 32 VDC
Pipe size: 23…400mm (0,91..15,7inch)
Pressure range: 3…10 barg (44 to 145 psig)
Temperature range (media): 135 to 180 °C (275...356 °F)
Output: 4-20mA active/passive according to NAMUR NE43pulse/frequency/binary
Input: Temperature
Communication protocol: Modbus RTUBACnet MS/TPHART®Modbus TCPM-BusBACnet IPUSBLAN
System configuration and installation: For more detailed Information please download the Technical Specifications